Air handling units with the air capacity up to 2200 m3/h and recuperation efficiency up to 88% in sound-proof and heat-insulated casing with electric heater.

Available modifications and technical parameters of VENTS VUT EH

ModelVUT 350 EHVUT 500 EHVUT 530 EHVUT 600 EH
Voltage [V / Hz]1~ 220-240 / 50-601~ 220-240 / 50-601~ 220-240 / 50-601~ 220-240 / 50-60
Maximum fan power [W]2pcs. х 1302pcs. х 1502pcs. х 1502pcs. х 195
Fan current [А]2pcs. х 0,62pcs. х 0,662pcs. х 0,662pcs. х 0,86
Electric heater power [kW]3344
Electric heater current [А]131317,417,4
Total unit power [kW]3,263,34,34,39
Total unit current [А]14,214,3218,7219,1
Air capacity [m3/h]350500530600
RPM1150110011001350
Noise level at 3m [dBA]24-4528-4728-4732-48
Transported air [°C]-25 up to +55-25 up to +50-25 up to +50-25 up to +55
Casing materialaluzincaluzincaluzincaluzinc
Insulation25 mm mineral wool25 mm mineral wool25 mm mineral wool25 mm mineral wool
Extract filterG4G4G4G4
Supply filterF7 (EU7)F7 (EU7)F7 (EU7)F7 (EU7)
Connected air duct diameter [mm]Ø125Ø150Ø160Ø200
Weight [kg]45494954
Heat recovery efficiencyup to 78 %up to 88 %up to 88 %up to 85 %
Heat exchanger typecross-flow typecross-flow typecross-flow typecross-flow type
SEC ClassEEEE
Heat exchanger materialaluminumaluminumaluminumaluminum

 

ModelVUT 800 EHVUT 1000 EHVUT 1500 EHVUT 2000 EH
Voltage [V / Hz]3~ 400 / 50-603~ 400 / 503~ 400 / 50-603~ 400 / 50-60
Maximum fan power [W]2pcs. х 2452pcs. х 4102pcs. х 4902pcs. х 650
Fan current [А]2pcs. х 1,082pcs. х 1,82pcs. х 2,152pcs. х 2,84
Electric heater power [kW]991818
Electric heater current [А]13132626
Total unit power [kW]9,499,818,9819,3
Total unit current [А]15,1616,630,331,7
Air capacity [m3/h]800120017502200
RPM1650185011001150
Noise level at 3m [dBA]48604965
Transported air [°C]-25 up to +45-25 up to +40-25 up to +45-25 up to +40
Casing materialaluzincaluzincaluzincaluzinc
Insulation50 mm mineral wool50 mm mineral wool50 mm mineral wool50 mm mineral wool
Extract filterG4G4G4G4
Supply filterG4 (F7*)G4 (F7*)G4 (F7*)G4 (F7*)
Connected air duct diameter [mm]Ø250Ø250Ø315Ø315
Weight [kg]85859696
Heat recovery efficiencyup to 78 %up to 78 %up to 77 %up to 77 %
Heat exchanger typecross-flow typecross-flow typecross-flow typecross-flow type
SEC ClassE---
Heat exchanger materialaluminumaluminumaluminumaluminum

*option

Detailed information on the VENTS VUT EH at our website.

Description

Air handling units VUT EH with electric heater are the complete air handling units designed to provide both supply and exhaust ventilation with air filtering and heat recovery. The exhaust air energy is used to heat up the supply fresh air through the heat exchanger. All the models are designed for connection with Ø 125, 150, 160, 200, 250, 315 mm round ducts.

Modifications

VUT EH – a range of compact energy saving air handling units (AHU) equipped with supply and exhaust centrifugal fans, cross-flow heat recovery elements, electric heating coils and air filters.

Casing

The casing is manufactured from aluminum-zinc compound with 25 mm thick mineral wool heat- and sound-insulating layer.

Filter

Two incorporated G4 panel filters for extract air ventilation and F7 filters for supply air ventilation are supplied with the unit.

Fans

The units are equipped with supply and exhaust centrifugal double-inlet fans with forward curved blades and built-in thermostat with automatic restart. The electric motors and impellers are dynamically balanced in two planes. The ball-bearings used with motors are designed for at least 40 000 hours operation and are maintenance-free.

Heat exchanger

The heat exchangers have high efficiency and are manufactured from aluminium plates. The unit is also equipped with the drain pan for condensate drainage.

Heater

The electric heater at outlet from the heat exchanger is designed for warming up of supply air up to the set level if heat recovery is not enough to attain the set supply air temperature.

Automation and control system

The unit incorporates an integrated automation and control system with a multi-functional control panel with LCD display. The standard delivery set includes 10 m connection cable for connection to the remote control panel. The unit has the freezing protection function to prevent the heat exchanger freezing by means of actuating the bypass damper and controlling water heater. As the temperature sensor warns of the freezing danger, the bypass air damper is opened and the intake air is directed through the air duct beside the heat exchanger. As the heat exchanger is warmed the supply air temperature rises up to the set level while passing through the heater. Meanwhile the warm extract air warms up the heat exchanger. After the freezing danger is no longer imminent, the bypass damper shuts the bypass duct and the unit reverts to the standard operation mode.

VUT EH control and protection functions

  • control from the control panel: switching on/off, speed selection, timer, faults;
  • maintaining the set room temperature by the sensor on the control panel – smooth heating capacity control;
  • three-speed fan speed control (low-medium-high);
  • unit operation according to daily and week schedule (timer adjustable from the control panel);
  • safe start-up/shutdown of the fans;
  • electric heater overheating protection by the temperature sensor installed in the supply air duct and by two overheating thermostats, one thermostat activated at 60 °C with automatic reset and another thermostat activated at 90 °C with manual reset. Blowing of the heating elements for heat removing at the end of the heating cycle;
  • filter clogging control by engine hours.

Mounting

The air handling unit is mounted on the floor, suspended to the ceiling by means of a seat angle with inserted vibration-damping element or attached to a wall with brackets. The unit can be mounted either in service spaces or in main premises above the suspended ceiling, in the pocket or can be placed directly in the room. Mounting in any position shall provide the correct condensate drainage. Access for the unit maintenance and filter cleaning shall be provided through the side panels.

Products from the category - Floor-mounted air handling units with heat recovery

 
 
 

On-site search

Search

Catalogue of products

Contacts

vents
(main office)

01030, Ukraine, Kyiv, Київ, М. Коцюбинського, 1
  • +38 (044) 406-36-XX

Sites

 
 

 
 

 
 
 
Write a message
Select message form:
 
 
 
Ідентифікатор сторінки
Ідентифікатор сторінки:
1234

Search
 
 

Close
 
 
Order a call
person
phone
email
record_voice_over
create