Negotiable price In stock
-
Specifications
Manufacturer | ВЕНТС |
Description VENTS VUT WH
Air handling units with the air capacity up to 2100 m3/h and recuperation efficiency up to 78% in sound-proof and heat-insulated casing with water heater.
Available modifications and technical parameters of VENTS VUT WH
Model | VUT 800 WH-2 | VUT 800 WH-4 | VUT 1000 WH-2 | VUT 1000 WH-4 |
---|---|---|---|---|
Voltage [V / Hz] | 1~ 220-240 / 50 | 1~ 220-240 / 50 | 1~ 220-240 / 50 | 1~ 220-240 / 50 |
Maximum fan power [W] | 2pcs. х 245 | 2pcs. х 245 | 2pcs. х 410 | 2pcs. х 410 |
Fan current [А] | 2pcs. х 1,08 | 2pcs. х 1,08 | 2pcs. х 1,8 | 2pcs. х 1,8 |
Number of water (glycol) coil rows | 2 | 4 | 2 | 4 |
Total unit power [kW] | 0,49 | 0,49 | 0,82 | 0,82 |
Total unit current [А] | 2,16 | 2,16 | 3,6 | 3,6 |
Air capacity [m3/h] | 780 | 780 | 1100 | 1100 |
RPM | 1650 | 1650 | 1850 | 1850 |
Noise level at 3m [dBA] | 48 | 48 | 60 | 60 |
Transported air [°C] | -25 up to +45 | -25 up to +45 | -25 up to +40 | -25 up to +40 |
Casing material | aluzinc | aluzinc | aluzinc | aluzinc |
Insulation | 50 mm mineral wool | 50 mm mineral wool | 50 mm mineral wool | 50 mm mineral wool |
Extract filter | G4 | G4 | G4 | G4 |
Supply filter | G4 (F7)* | G4 (F7)* | G4 (F7)* | G4 (F7)* |
Connected air duct diameter [mm] | Ø250 | Ø250 | Ø250 | Ø200 |
Weight [kg] | 88 | 88 | 88 | 88 |
Heat recovery efficiency | up to 78 % | up to 78 % | up to 78 % | up to 78 % |
Heat exchanger type | cross-flow type | cross-flow type | cross-flow type | cross-flow type |
SEC Class | E | E | - | - |
Heat exchanger material | aluminum | aluminum | aluminum | aluminum |
Model | VUT 1500 WH-2 | VUT 1500 WH-4 | VUT 2000 WH-2 | VUT 2000 WH-4 |
---|---|---|---|---|
Voltage [V / Hz] | 3~ 400 / 50 | 3~ 400 / 50 | 3~ 400 / 50 | 3~ 400 / 50 |
Maximum fan power [W] | 2pcs. х 490 | 2pcs. х 490 | 2pcs. х 650 | 2pcs. х 650 |
Fan current [А] | 2pcs. х 2,15 | 2pcs. х 2,15 | 2pcs. х 2,84 | 2pcs. х 2,84 |
Number of water (glycol) coil rows | 2 | 4 | 2 | 4 |
Total unit power [kW] | 0,98 | 0,98 | 1,3 | 1,3 |
Total unit current [А] | 4,3 | 4,3 | 5,68 | 5,68 |
Air capacity [m3/h] | 800 | 1200 | 1750 | 2200 |
RPM | 1700 | 1700 | 2100 | 2100 |
Noise level at 3m [dBA] | 49 | 49 | 65 | 65 |
Transported air [°C] | -25 up to +45 | -25 up to +45 | -25 up to +40 | -25 up to +40 |
Casing material | aluzinc | aluzinc | aluzinc | aluzinc |
Insulation | 50 mm mineral wool | 50 mm mineral wool | 50 mm mineral wool | 50 mm mineral wool |
Extract filter | G4 | G4 | G4 | G4 |
Supply filter | G4 (F7*) | G4 (F7*) | G4 (F7*) | G4 (F7*) |
Connected air duct diameter [mm] | Ø315 | Ø315 | Ø315 | Ø315 |
Weight [kg] | 99 | 99 | 99 | 99 |
Heat recovery efficiency | up to 77 % | up to 77 % | up to 77 % | up to 77 % |
Heat exchanger type | cross-flow type | cross-flow type | cross-flow type | cross-flow type |
Heat exchanger material | aluminum | aluminum | aluminum | aluminum |
*option
Detailed information on the VENTS VUT WH at our website.
Description
Air handling units VUT WH with water heater are the complete air handling units designed to provide both supply and exhaust ventilation with air filtering and heat recovery. The exhaust air energy is used to heat up the supply fresh air through the heat exchanger. All the models are designed for connection with Ø 125, 150, 160, 200, 250, 315 mm round ducts.
Modifications
VUT WH – a range of compact energy saving air handling units (AHU) equipped with supply and exhaust centrifugal fans, cross-flow heat recovery elements, water or glycol heating coils and air filters.
Casing
The casing is manufactured from aluminum-zinc compound with 25 mm thick mineral wool heat- and sound-insulating layer.
Filter
Two incorporated G4 panel filters for extract air ventilation and F7 filters for supply air ventilation are supplied with the unit.
Fans
The units are equipped with supply and exhaust centrifugal double-inlet fans with forward curved blades and built-in thermostat with automatic restart. The electric motors and impellers are dynamically balanced in two planes. The ball-bearings used with motors are designed for at least 40 000 hours operation and are maintenance-free.
Heat exchanger
The heat exchangers have high efficiency and are manufactured from aluminium plates. The unit is also equipped with the drain pan for condensate drainage.
Heater
The water heater at outlet from the heat exchanger is designed for warming up of supply air up to the set level if heat recovery is not enough to attain the set supply air temperature. The water heaters are designed for max. operating pressure 1.0 MPa (10 bar) and max. heat medium operating temperature 95 °C.
Automation and control system
The unit incorporates an integrated automation and control system with a multi-functional control panel with LCD display. The standard delivery set includes 10 m connection cable for connection to the remote control panel. The unit has the freezing protection function to prevent the heat exchanger freezing by means of actuating the bypass damper and controlling water heater. As the temperature sensor warns of the freezing danger, the bypass air damper is opened and the intake air is directed through the air duct beside the heat exchanger. As the heat exchanger is warmed the supply air temperature rises up to the set level while passing through the heater. Meanwhile the warm extract air warms up the heat exchanger. After the freezing danger is no longer imminent, the bypass damper shuts the bypass duct and the unit reverts to the standard operation mode.
VUT WH control and protection functions
- control from the control panel: switching on/off, three-speed fan selection, selecting heating/cooling modes (if connected to duct heater); room temperature display;
- maintaining supply air temperature set from the control panel by controlling the circulation pump and actuating the heat medium regulating valve; input from the heat medium flow switch (pump alarm);
- safe start-up/ shutdown of the fans, warming up of the water heater before start-up; return heat medium temperature control when the fan is off;
- freezing protection of the water heating coils by the exhaust temperature sensor and the return heat medium temperature sensor;
- control of the compressor and condensing unit of the water cooler by the room temperature sensor (for the models equipped with a duct air cooler);
- actuating the external air dampers with a return spring;
- unit operation according to week schedule (set at the system setup);
- unit shut down at signal from the fire alarm system;
- smooth bypass damper control in the bypassing mode to prevent the heat exchanger freezing.
Mounting
Die Lüftungsanlage ist für die Innenraummontage ausgelegt. Die Montageposition der Lüftungsanlage muss Kondensatansammlung und Kondensatablauf sichern. Der Wartungszugang für die Servicearbeiten und Filterreinigung ist über die Seitenblenden, links auf die Zuluftstromrichtung gesehen. Für VUT 1500 WH und VUT 2000 WH kann der Wartungszugang von links sowie von rechts vorgesehen werden. Die Wartungsseite beim Auftrag angeben.
Options
For attenuation of sound generated by the fans it is recommended to install the duct silencer (refer SR) from inside before the unit. For vibration absorbing it is recommended to install the flexible antivibration connectors (refer VVG) on both sides of the unit. The mixing units USWK are recommended for smooth supply air temperature regulation in the units equipped with water heaters. The mixing unit USWK with three-way heat medium regulating valve and circulation pump provides smooth heating capacity regulation and minimizes the water heater freezing danger.
Products from the category - Floor-mounted air handling units with heat recovery
Компания осуществляет возврат в соответствии с Законом «О защите прав потребителей»
Срок возврата: 14 дней.
Стоимость возврата: за счет покупателя.
Возврат товара надлежащего качества
Условия возврата по Закону: товар не был в употреблении, не вскрыта упаковка, сохранен товарный вид и потребительские свойства (в исправном состоянии).
Если условия не выполнены, по закону вам откажут в возврате или обмене.
В случае обмена или возврата товара, все транспортные затраты клиент берет на себя.
Обмен на такой же товар или возврат средств за товар.
Возврат товара не надлежащего качества
Проверяйте свой заказ непосредственно на почте, при получении. В случае, если Вы видите, что упаковка товара повреждена или товар находится в нерабочем состоянии или он не подходит Вам по каким либо причинам или внешне есть признаки того, что товар пришел в негодность из-за не качественного оказания перевозчиком своих услуг, неполная комплектация ― отказывайтесь от него прямо на почте и в письменном виде заявите перевозчику причину такого отказа, составляйте АКТ. Покупателям, которые не выполнили данное условие будет отказано в обмене товара или возврате денежных средств ввиду отсутствия вины и непричастности магазина к повреждению товара и нарушению целостности его упаковки.
On-site search
Contacts
vents
(main office)
01030, Ukraine, Kyiv, Київ, М. Коцюбинського, 1 |
|